Thermokon

PR25

PR25+ PT1000 T100 L1000

Application/type Cable sensor, Surface sensor
Purpose Measure values
Measured values temperature
Interface Passive
Sensor SI-Protection against permeation of humidity and mechanical stress (e.g. vibration), PT1000 DIN cl. B, passive
Operating range temperature (°C) -35..+100
Operating ranges temperature (°C) -35..+100
Operating range temperature enclosure (°C) -35..+90
Operating range humidity max. 85% rH short term condensation
Accuracy temperature ±0,3 K (typ. at 0 °C)
Material in touch with media Sensor probe, Ø=11/15 mm, aluminium, hex pressed (IP65)
Installation length (mm) 28
Enclosure USE-S, impact- and shock-resistant enclosure with quick-release cover, PC
Colour pure white
Protection (IP) IP65, according to EN 60529
Connection removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable plug-in terminal, max. 2,5 mm²
Connection cable PVC, 0,25 mm², 2-wire
Length connection wire (m) 1
Delivery content incl. mounting base enclosure USE-S pure white, incl. fixing kit rawlplugs and screws (2x each)
Packaging length (mm) 170
Packaging width (mm) 120
Device length (mm) 63
Device width (mm) 68
Device height (mm) 40
Top