Thermokon

TF14+

TF14+ TRA MultiRange T180 050.04 L1000

Cable sensor -50..+180 °C | Active, 4..20 mA | silicone, 0,14 mm², 2-wire, 1 m
Sensor probe, Ø=4 mm, stainless steel V4A (1.4571), 16-point pressed (IP65)

Application/type Cable sensor
Purpose Measure values
Measured values temperature
Interface Active, 4..20 mA
Configuration jumper
Sensor SI-Protection against permeation of humidity and mechanical stress (e.g. vibration)
Output current 4..20 mA, max. load 500 Ω
Operating range temperature (°C) -50..+180
Operating ranges temperature (°C) -50..+180
Output signal temperature scaling analogue output, 0..+160 °C (default setting), selectable from 4 temperature ranges -50..+50 | -20..+80 | -15..+35 | -10..+120 | 0..+50 | 0..+100 | 0..+160 | 0..+250 °C, adjustable at the transducer
Operating range temperature enclosure (°C) -30..+70
Operating range humidity max. 85% rH short term condensation
Accuracy temperature ±0,5 K (typ. at 21 °C), within default measuring range, potentiometer for offset adjustment
Power supply 15..24 V = (±10%) SELV
Power consumption max. 0,5 W (24 V =)
Material in touch with media Sensor probe, Ø=4 mm, stainless steel V4A (1.4571), 16-point pressed (IP65)
Installation length (mm) 50
Enclosure USE-S, impact- and shock-resistant enclosure with quick-release cover, PC
Colour pure white
Protection (IP) IP65, according to EN 60529
Connection removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable plug-in terminal, max. 2,5 mm²
Connection cable silicone, 0,14 mm², 2-wire
Length connection wire (m) 1
Delivery content incl. mounting base enclosure USE-S pure white, incl. mounting set (screws and accessories)
Packaging length (mm) 170
Packaging width (mm) 120
Device length (mm) 63
Device width (mm) 68
Device height (mm) 40
Top